Control Functions (P111)

Each relay can be configured independently to take advantage of the MultiRanger’s advanced features and flexibility. Start with a preset application and then change the required parameters to make the task more efficient.

Setpoints (P112, P113)

Each relay is triggered by one or more setpoints. The setpoints can be based on absolute level (P112, P113) or rate of change (P702, P703). Each control function specifies which setpoints are required.

P100 Preset Applications [MR 200]

Six preset applications to configure or bench test the unit.

Primary Index

Global

 

 

0

*

OFF

 

 

 

 

 

1

 

Wet Well 1

 

 

 

 

 

2

 

Wet Well 2

Values

 

 

 

3

 

Reservoir 1

 

 

 

 

 

4

 

Reservoir 2

 

 

 

 

 

5

 

Screen

 

 

 

 

 

6

 

Alarms

 

P110 Level Source

 

P111 Relay Control Function

Alters

P112 Relay On Setpoint

 

P113 Relay OFF Setpoint

 

P121 Pump by Rate

Related

P001 Operation

 

 

 

 

Select an application that is similar to yours and change the parameters required. If none suit, then refer to P111 Relay Control Function on page 134.

Note: Programming the relays independently is the most common method used.

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 133

Parameters

Page 143
Image 143
Siemens 200 instruction manual P100 Preset Applications MR, Control Functions P111, Setpoints P112, P113