Siemens 200 instruction manual Quick Start P001 to P007, P000 Lock, P001 Operation

Models: 200

1 282
Download 282 pages 42.81 Kb
Page 129
Image 129

P000 Lock

Notes:

This lock only applies to the handheld programmer: it does not lock access through communications.

A remote master can change configuration if P799 is set to allow this.

Secures the MultiRanger from changes via the handheld programmer.

Primary Index

Global

 

 

 

 

1954

*

OFF (programming permitted)

 

 

 

 

Values

-1

 

Simulation Controls (relays energize based on simu-

 

lated level)

 

 

 

 

 

 

 

 

other

 

lock activated (programming secured)

Related

 

 

Simulation on page 85

 

 

 

 

 

WARNING:

Use this lock as backup security only. It uses a fixed value which can be discovered by unauthorized personnel.

Access this parameter directly (type 000) and enter any value (except 1954) to secure programming lock. To unlock the MultiRanger, access this parameter and enter 1954.

Quick Start (P001 to P007)

P001 Operation

Sets the type of measurement required for the application.

Primary Index

Single Point Model

 

Dual Point Model

Global

 

 

Transducer

 

 

 

 

0

 

Out-of-service

 

 

 

 

 

 

 

1

 

Level – how full the vessel is (MR 200: volume – P050)

 

 

 

 

 

2

 

Space – how empty the vessel is (MR 200: ullage – P050)

 

 

 

 

Values

3

*

Distance – distance from transducer to material

 

 

 

 

 

4

 

DPD – dual point difference [MR 200]

 

 

 

 

 

 

 

5

 

DPA – dual point average [MR 200]

 

 

 

 

 

6

 

OCM – flow rate in an open channel [MR 200]

 

 

 

 

 

7

 

Pump Totalizer – total pumped volume [MR 200]

Alters

P600

Primary Measuring Device

 

 

 

 

 

 

 

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 119

Parameters

Page 129
Image 129
Siemens 200 instruction manual Quick Start P001 to P007, P000 Lock, P001 Operation, Single Point Model Dual Point Model