Parameters

P052 Tank Dimension A [MR 200]

Dimension A as used in P050 Tank Shape.

Primary Index

Level

Values

Range: 0.0 to 99.00 m (or equivalent depending on units)

 

 

Preset: 0.000

 

Related

P050 Tank Shape

 

 

 

Enter one of the following:

height of the tank bottom if P050 = 2,3,4, or 5

OR

length of one end section of the tank if P050 = 7, in Units (P005)

P053 Tank Dimension L [MR 200]

Dimension L as used in P050 Tank Shape.

Primary Index

Level

Values

Range: 0.0 to 99.00 m (or equivalent depending on units)

 

 

Preset: 0.000

 

Related

P050 Tank Shape

 

 

 

Enter the following:

tank length (excluding both end sections) if P050 = 7

P054 Level Breakpoints (Universal Volume Calculation) [MR 200]

When the tank shape is too complex for any of the preconfigured shapes, you can specify the volume based on segments. See “Accessing a Secondary Index” on page 117 for more information.

Primary Index

Level

Secondary Index

Breakpoint

Values

Range: 0.0 to 99.00 m or Max. volume (P051) (or equivalent depending on

units)

 

Related

P055 Volume Breakpoints

 

 

 

Enter the following:

up to 32 level breakpoints (where volume is known) if P050 = 9 or 10

Entering a Level Breakpoint

1.Go to Parameter P054.

2.For each index enter a breakpoint in measurement units.

3.Ensure that each breakpoint corresponds to the same index for P055.