Siemens 200 instruction manual P131 Pump Run-On Duration MR, P132 Pump Start Delay MR

Models: 200

1 282
Download 282 pages 42.81 Kb
Page 152
Image 152

Parameters

P131 Pump Run-On Duration [MR 200]

Sets the number of seconds that the pump runs on.

Primary Index

Relay

 

 

Values

Range: 0.0 to 9999

 

 

Preset: 0.000

 

 

 

 

Related

Advanced Pump Control Modifiers (P130 to P136)

 

 

 

Your pump capacity determines the amount of material that can be removed. Choose a value long enough to clean out the vessel bottom, yet short enough not to run the pump dry. Also be sure that this value does not overlap with P130 (Interval). The timing should look something like this:

 

 

 

 

 

P131

 

 

P130 (Pump Run-On)

 

 

 

P132

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P132 Pump Start Delay [MR 200]

Sets the minimum delay (in seconds) between pump starts.

Primary Index

Global

 

 

 

Range: 0.0 to 9999

Values

 

Preset: 10 seconds

 

 

 

Value is divided by 10 in simulation mode.

 

 

 

Related

Advanced Pump Control Modifiers (P130 to P136)

P121 Pump by Rate

 

 

 

 

Use this feature to reduce a power surge from all pumps starting at the same time. This delay determines when the next pump is permitted to start.

P133 Pump Power Resumption Delay [MR 200]

Sets the minimum delay before the first pump restarts after power failure.

Primary Index

Global

 

 

Values

Range: 0.000 to 9999

 

 

Preset: 10 seconds

 

 

 

 

Related

Advanced Pump Control Modifiers (P130 to P136)

P132 Pump Start Delay

 

 

 

 

This reduces the surge from the first pump starting immediately on power resumption. When this delay expires, other pumps will start as per P132.

Page 142

MultiRanger 100/200 – INSTRUCTION MANUAL

7ML19981FB06

Page 152
Image 152
Siemens 200 instruction manual P131 Pump Run-On Duration MR, P132 Pump Start Delay MR, P133 Pump Power Resumption Delay MR