Alarms

In Bounds/ Out of Bounds Range [MR 200]

Use the bounded range alarms to detect when the level is inside or outside of the range. By using a bounded range alarm, you can effectively put two level alarms (high and low) on one relay.

Setting an Out of Bounds Alarm

Parameter

Index

Value

P111

5

3

P112

5

1.3

P113

5

0.3

P116

5

0.05

Results:

Trips alarm above 1.35 m and below 0.25m

Resets alarm below 1.25 m and above 0.35m

Setting an In Bounds Alarm

Parameter

Index

Value

P111

5

2

P112

5

1.3

P113

5

0.3

P116

5

0.05

Results:

Trips alarm below 1.25 m and above 0.35 m

Resets alarm above 1.35 m and below 0.25 m

Cable Fault

Activates an alarm if transducer cable circuit enters a shorted or opened state.

Parameter

Index

Value

Description

P111

5

7

Alarm on transducer cable fault

P110

5

1

Alarm on Transducer One

Temperature [MR 200]

Use the temperature alarm to activate an alarm when the temperature reaches the ON setpoint (P112). This alarm uses the same setpoint parameters as the level alarms (P112 and P113).