P664 Temperature

View the transducer temperature in °C.

 

Primary Index

 

Transducer

 

 

 

 

 

Values

 

Range: -50 to 150 (view only)

 

 

 

 

 

 

Altered By

 

P660 Temp Source

 

 

 

 

 

 

 

 

• P651

Sound Velocity Calibration

 

Related

 

P653

Velocity

 

 

• P654

Velocity at 20°C

 

 

 

 

 

 

P661 Temp Fixed

 

 

 

 

 

Value is displayed when

 

is pressed in RUN mode (see Readings in Run Mode on

page 23).

 

 

 

If Temp Source (P660) is set to any value other than Fixed Temp, the value displayed is the temperature measured. If Temp Source is set to Fixed Temp, the P661 value is displayed.

Rate (P700 to P708)

These parameters determine how material level changes are reported.

P700 Max Fill Rate

Adjusts the MultiRanger response to increases in the actual material level (or advance to a higher Failsafe Material Level, P071).

Primary Index

 

Single Point Model

Dual Point Model

 

 

 

Global

Transducer

 

 

 

 

Values

Range: 0.000 to 99.00 m (or equivalent depending on units)

 

 

 

Altered by

P003 Maximum Process Speed

 

 

 

 

 

P005 Units

 

Related

P007 Span

 

 

• P071 Failsafe Material Level

 

 

 

 

 

Enter a value slightly greater than the maximum vessel filling rate. This value, in Units (P005) or % of Span (P007) per minute, is automatically altered when Maximum Process Speed (P003) is altered.

P003 Value

Meters/Minute

1

0.1

 

 

2

1

3

10

 

 