Wiring

Terminal Board

The terminal board on the MultiRanger allows all inputs and outputs to be connected simultaneously.

Note: Recommended torque on terminal clamping screws.

0.56 - 0.79 Nm

5 - 7 in.lbs

Please do not overtighten the screws.

 

 

 

 

TB1

TB2

 

 

L2/N

L1

 

 

TB1

2

 

 

 

 

 

 

TB3

 

 

 

 

1

 

 

 

SYNC

 

 

 

 

 

12-30 V

 

mA INPUT

 

 

 

 

DC Version

 

SHIELD

 

 

 

RELAY 1

 

 

 

1

 

 

 

 

 

 

 

4 - 20 mA

RELAY 2

 

 

OUTPUTS

 

 

 

2

 

 

 

 

RELAY 3

 

 

TS-3

 

 

 

 

 

 

SHIELD

RELAY 4

 

 

 

1

 

 

 

 

 

 

 

DISCRETE

2

 

 

 

INPUTS

 

RELAY 5

 

 

 

 

 

 

 

 

COM

RELAY 6

 

 

RS485 A

 

 

 

 

B

Cables

The MultiRanger transceiver requires a shielded two-wire connection to the transducer.

Connection

Cable Type

mA input and mA output

2 copper conductors, twisted, with shield1/drain wire,

sync, Temperature sensor,

300V 0.324 - 0.823 mm2 (22 - 18 AWG)

discrete input, dc input

Maximum length: 365 m

Transducer

 

 

Do not use a coaxial transducer cable extension with the

 

MultiRanger. Electrical noise interference affects

 

performance.

Relay output

Relay to be copper conductors per local requirements to

AC input

meet 250 V 5A contact rating.

1.Preferred shielding is braided screen.

Page 16

MultiRanger 100/200 – INSTRUCTION MANUAL

7ML19981FB06