P708 Volume Rate Display [MR 200]

The rate of change of volume in percent of maximum volume per minute.

Please note that this feature applies to the MultiRanger 200 only.

Primary Index

Single Point Model

Dual Point Model

 

 

Global

Transducer

 

 

 

 

Values

Range: -999 to 9999 (view only)

 

 

 

Related

• P622 Inflow / Discharge Adjust

 

 

 

This value is used internally to calculate inflow in pumped volume applications (P622=3).

Press READING to toggle between percent and volume.

Measurement Verification (P710 to P713)

P710 Fuzz Filter

Use this to stabilize the reported level, due to level fluctuations (such as a rippling or splashing liquid surface) within the Echo Lock Window (P713).

Primary Index

Single Point Model

Dual Point Model

 

 

Global

Transducer

 

 

 

 

Values

Range: 0 to 100 (0 = off)

 

 

 

Altered by

• P003 Maximum Process Speed

 

 

 

Related

• P007 Span

 

• P713 Echo Lock Window

 

 

 

 

 

 

This value (in % of Span, P007) is automatically altered when Maximum Process Speed (P003) is altered. The higher the value entered, the greater the fluctuation stabilized.