Parameters

P212 mA Output Min Limit

Sets the minimum mA output value (in mA) to be produced.

Primary Index

mA output

 

 

Values

Range: 0.000 to 22.00

 

 

Preset: 3.8

 

 

 

 

Related

P200 mA Output Range

P213 mA Output Max Limit

 

 

 

 

P213 mA Output Max Limit

Sets the maximum mA output value (in mA) to be produced.

Primary Index

mA output

 

 

Values

Range: 0.000 to 22.00

 

 

Preset: 20.2 mA

 

 

 

 

Related

P200 mA Output Range / P212 mA Output Min LImit

 

 

 

mA Output Trim (P214 to P215)

This does not affect the P203 value shown, and is used when recalibration of an external device is impractical.

To adjust the value so that the device correctly indicates 4.00 (when P214 is accessed) or

20.00 mA (when P215 is accessed):

1.Attach ammeter to MultiRanger 4 to 20 mA output.

2.Access P214, Index 1 (for mA output 1) or 2 (for mA output 2). Press CLEAR and

ENTER

. The ammeter should show a value near 4 mA.

3.Enter the exact value displayed on the ammeter into P214 (Index 1 or 2).

4.The ammeter should then read exactly 4.00 mA.

5.Repeat steps 1 to 4 to set P215, using 20 mA as the desired value.

P214 4 mA Output Trim

Calibrates the 4 mA output.

Primary Index

mA output

 

 

Values

Preset: 4.00

 

 

 

Related

P215 20 mA Output Trim

 

 

 

Adjust this value so the device indicates 4.000 mA when P214 is accessed.