Parameters

P801 Range Extension

Allows the material level to fall below the Empty setting without reporting LOE.

Primary Index

 

Single Point Model

Dual Point Model

 

 

 

Global

Transducer

 

 

 

 

 

Range: 0.000 to 99.00 m, or max. span (P007), or equivalent

Values

depending on units

 

 

 

 

 

Preset: 20% of Span (P007)

 

 

 

 

 

 

P005 Units

 

Related

P006 Empty

 

P007 Span

 

 

 

 

P004 Transducer

 

 

 

 

 

This feature is useful in OCM applications where the Empty level is set to the bottom of the weir, and above the bottom of the channel, and should be used if the surface monitored can fall past the Empty (P006) level in normal operation. The value is added to Empty (P006) and can be greater than the range of the transducer. If the surface monitored can extend beyond Empty (P006), increase Range Extension (in Units (P005) or

%of Span) such that Empty plus Range Extension is greater than the transducer face to furthest surface to be monitored distance. This is often the case with OCM when using weirs and some flumes.

P802 Transducer with Submergence Shield

Used when the transducer is expected to be submerged on occasion.

Primary Index

 

Single Point Model

Dual Point Model

 

 

 

 

 

Global

Transducer

 

 

 

 

 

 

 

Values

0

 

*

Off

 

 

 

 

 

 

1

 

 

Submergence transducer

 

 

 

 

 

 

 

 

 

 

 

P006 Empty

 

Related

 

P071 Failsafe Material Level

 

 

 

Relays

 

 

 

 

 

 

 

When a transducer with a submergence shield is submerged, the shield traps an air pocket that creates a special echo. The MultiRanger recognizes the echo and advances the reading to the highest level and operates displays and outputs accordingly. This feature is effective for when power is returned while the transducer is submerged.