Siemens 200 Non-Transducer Noise Sources, Common Wiring Problems, Reducing Electrical Noise

Models: 200

1 282
Download 282 pages 42.81 Kb
Page 243
Image 243

Non-Transducer Noise Sources

Remove all input and output cables from the MultiRanger individually while monitoring the noise. If removing a cable reduces the noise, that cable may be picking up noise from adjacent electrical equipment. Check that low voltage cables are not being run adjacent to high voltage cables or near to electrical noise generators such as variable speed drives.

Filtering cables is an option but is not recommended unless all other options have been exhausted.

The MultiRanger is designed to work near heavy industrial equipment such as variable speed drives. Even so, it should not be located near high voltage wires or switch gear.

Try moving the electronics to a different location. Often moving the electronics a few meters farther from the source of noise will fix the problem. Shielding the electronics is also an option, but it should be a last resort. Proper shielding is expensive and is difficult to install properly–the shielding box must enclose the MultiRanger electronics completely, and all wires must be brought to the box through grounded metal conduit.

Common Wiring Problems

Make sure that the transducer shield wire is connected at the electronics end only. Do not ground it at any other location.

Do not connect the transducer shield wire to the white wire.

The exposed transducer shield wire must be as short as possible.

Connections between the wire supplied with the transducer, and any customer installed extension wire should be done in grounded metal junction boxes.

On Siemens Milltronics transducers the white wire is negative and the black wire is positive. If the extension wire is colored differently, make sure that it is wired consistently.

Extension wire must be shielded twisted pair. Older MultiRanger products may have included recommendations to use co-axial cable for noise reduction purposes. This is no longer the case. Use shielded twisted pair. See the installation section for specifications.

Reducing Electrical Noise

Ensure that the transducer cable does not run parallel to other cables carrying high voltage or current.

Move the transducer cable away from noise generators like variable speed drives.

Put the transducer cable in grounded metal conduit.

Filter the noise source.

Reducing Acoustical Noise

Move the transducer away from the noise source.

Use a stilling well.

Install a rubber or foam bushing or gasket between the transducer and the mounting surface.

Relocate or insulate the noise source.

Change the frequency of the noise. The MultiRanger is only sensitive to noise between 25 KHz and 65 KHz.

Appendix C: Troubleshooting

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 233

Page 243
Image 243
Siemens 200 Non-Transducer Noise Sources, Common Wiring Problems, Reducing Electrical Noise, Reducing Acoustical Noise