Page 230 MultiRanger 100/200 – INSTRUCTION MANUAL 7ML19981FB06
mmmmm
Appendix B: Tech Reference
For combination curves, enter at least 2 breakpoints immediately before and after any
sharp angle (as well as 1 breakpoint exactly at the angle) on the curve. For more
information, go to

Typical Flow Characterization

on page83.
Maximum Process Speed
The MultiRanger’s ability to respond to material level changes is designed to exceed even
the most demanding installation requirements.
The Maximum Process Speed setting automatically presets various parameters affecting
the MultiRanger response to material level changes as follows:
If any of these parameters are independently altered, a Maximum Process Speed (P003)
parameter alteration automatically resets the independently altered value.
Slower Maximum Process Speed (P003) provides greater measurement reliability. Faster,
independently set Max Fill (P700) and Max Empty (P701). Rates may be impeded by Echo
Lock (P711), Scan Delay (P727), and Shot Delay (P728) values.

Paramete r Values Dependent on Maximum Process

Speed (P003)

(units) 1 (slow) 2 (medium) 3 (fast)

P070 Failsafe Timer (min) 100 10 1
P700 Max Fill Rate (m/min) 0.1 110
P701 Max Empty Rate (m/min) 0.1 1 10
P702 Filling Indicator (m/min) 0. 01 0.1 1
P703 Emptying Indicator (m/min) 0.01 0.1 1
P704 Rate Filter (option) 4 2 2
P710 Fuzz Filter (% of Span) 100 50 10
P713 Echo Lock Window (per P701 / P702 and time since last valid measurement)
P727 Scan Delay (seconds) 5 5 3
P841 Long Shot Number 10 5 2