7ML19981FB06 MultiRanger 100/200 – INSTRUCTION MANUAL Page 45
mmmmm
Relays
[MR 100]: Functions affected by setpoint are configured by parameters that determine the
application requirements such as timing.

P111 Pump and Control functions

(see page 134)
sets the functions requirements.
[MR 200]: Functions affected by setpoint are configured by parameters that determine the
application requirements such as timing.

P111 Pump and Control functions

(see page 134
sets the function requirements. Other function parameters:
P132–Pump Start Delay
P133–Pump Power Resumption Delay
P645–Relay Duration

Relay Logic is Modified

Normal operating conditions means that alarms are off and pumps are on. This can be
reversed using P118–Relay Output Logic.
Relay Failsafe

P129–Relay Failsafe

Adjusts how individual relays react to a failsafe condition. Relays can be set to:
OFF Control is by P071–Failsafe Material Level
HOLd Keeps the relay in the current state
dE De-energizes the relay (default for pump controls)
En Energizes the relay