The MultiRanger is pre-programmed for common PMD flow calculations. If your PMD is not listed, select the appropriate Universal Flow Calculation.

Associated parameters Max Head (P603), Max Flow (P604), and Min Head (P605) may be scroll accessed. If Operation is not set for OCM (P001 = 6), this value is preset to 0. If Operation is set for OCM, it is preset to 1.

P601 Flow Exponent [MR 200]

The Exponent for the flow calculation formula.

Primary Index

 

Single Point Model

Dual

 

 

 

Global

Transducer

 

 

 

 

Values

Range: -999 to 9999

 

 

 

 

Preset: 1.55

 

 

 

 

 

 

Altered By

P600 Primary Measuring Device

 

 

 

 

 

P603 Maximum Head

 

Related

P604 Maximum Flow

 

 

P605 Zero Head

 

 

 

 

 

Use this parameter if the Primary Measuring Device (P600) is set to 1 (exponential). It creates an exponential curve with end points set by Max Head (P603) and Zero Head (P604) and with the curve based on the specified exponent.

If P601 = 1, the flow characteristic is a straight line

Max. Flow

(P604)

Zero Flow

Zero Head

Max. Head (P603)

A Word on Exponents

The exponential equation is

Q= KHP601

Where:

Q = flow

K = internal constant

H = head

Parameters

Use the exponent specified by the PMD manufacturer, if available, or the sample value given below.

Page 166

MultiRanger 100/200 – INSTRUCTION MANUAL

7ML19981FB06