P799 Communications Control

Enables the read/write access to parameters via remote communications.

 

Protocol

 

Primary Index

(Index 1 controls the Modbus Master (RS-485 or RS-232); Index 2

controls the Fieldbus Master (PROFIBUS DP, DeviceNet, or Allen

 

 

Bradley Remote I/O)

 

 

 

 

 

0

 

Read Only

 

 

 

 

Values

1

*

Read/Write

 

 

 

 

2

 

Restricted Access – read only except for P799 which is

 

 

read/write

 

 

 

 

 

 

 

Notes:

P799 controls the lock access via communications.

P000 controls the lock access via the Siemens handheld programmer.

Echo Processing (P800 to P807)

P800 Near Blanking

The space near the transducer face which cannot be measured.

Primary Index

 

Single Point Model

 

Dual Point Model

 

 

 

 

 

Global

 

 

Transducer

 

 

 

 

 

 

 

Range: 0.000 to 99.00 m (or equivalent depending on units)

Values

 

 

 

Preset:

0.300m (Most transducers)

 

 

 

 

0.450m (XCT-8, XCT-12)

 

 

 

 

 

 

P006 Empty

 

Related

P007 Span

 

 

• P833 TVT Start Min

 

 

 

 

 

 

 

Use this feature if the surface is reported to be near the transducer face but is in fact much further away. Extend this value when changing transducer location, mounting, or aiming.

Please note that changing the Near Blanking cannot correct measurement problems. Ensure that Span (P007) < Empty (P006) minus Near Blanking (P800)

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 199