Set Relays to FIRST IN FIRST OUT (FIFO) ASSIST [MR 200]

Parameter

Index

 

Value

 

Description

 

 

P111

1

56

 

Sets the pump relays (index 1, 2, and 3) to

P111

2

56

 

FIFO DUTY ASSIST.

P111

3

56

 

 

Set the Relay ON Setpoints [MR 200]

 

 

 

 

 

 

Parameter

Index

 

Value

 

Description

P112

1

 

0.4m

 

Sets the three setpoints for the pump relays.

P112

2

 

0.3m

 

The first cycle will use these setpoints.

P112

3

 

0.2m

 

Subsequent cycles rotate the setpoints

 

 

 

 

 

among the pumps.

Set the Relay OFF Setpoints [MR 200]

 

 

 

 

 

 

Parameter

Index

 

Value

 

Description

P113

0

 

1.3m By using index 0 all six relays are set at the

 

 

 

 

 

same time, including any alarm relays. Use

 

 

 

 

 

with caution.

Optional Pump Controls

Starting Pumps by Rate of Level Change [MR 200]

Use this function when multiple pumps will be controlled by rate of level change rather than setpoints. Pumping costs can be reduced because only the highest ON setpoint needs to be programmed. This results in a lower difference in head to the next wet well which, in turn, results in less energy being used to pump out the well.

Pump Control

Parameter

P112

P112

P112

P113

P113

P113

P121

P121

P121

P132

Index

1

2

3

1

2

3

1

2

3

G

Value Description

1.35Starting pumps by rate allows all setpoints to

1.35be set higher to save money by pumping from

1.35the highest safe level of the wet well.

0.5m

Notice that all indexed relays for both P112

0.5m

and P113 are set to the same levels.

0.5m

 

1

The pumps will start on 20 second intervals

1

until the rate set in P703 is met.

1

 

20.0

 