P608 Flowrate Units [MR 200]

The volume units used to display total flow.

Note: Set this parameter only when using BS-3680/ISO 4359 Rectangular Flume or BS-3680/ISO 1438/1 Thin Plate V-Notch Weir (P600 = 6 or 7). Use the default value of 0 for P608 when P600 = 1 to 5.

Primary Index

 

Single Point Model

 

Dual Point Model

 

 

 

 

 

Global

 

Transducer

 

 

 

 

 

 

 

Ratiometric (P600=all)

 

 

 

 

 

 

 

0

*

Ratiometric calculation (units defined by P604)

 

 

 

 

 

 

 

Absolute (P600=6,7 only)

 

 

 

 

 

 

 

 

1

 

litres / second

 

Values

 

 

 

 

2

 

cubic metres / hour

 

 

 

 

 

 

 

3

 

cubic metres / day

 

 

 

 

 

 

 

4

 

cubic feet / second

 

 

 

 

 

 

 

5

 

gallons / minute – Imperial

 

 

 

 

 

 

6

 

million gallons / day – Imperial

 

 

 

 

 

Values

7

 

gallons / minute – U.S.

 

 

 

 

 

 

8

 

million gallons / day – U.S.

 

 

 

 

 

 

 

 

 

 

Alters

P606 Time Units

 

 

 

 

Altered By

P600 Primary Measuring Device

 

 

 

 

Related

P608 Flowrate Units

 

 

 

 

 

 

 

This parameter is enabled only if the primary measuring device (PMD) supports absolute calculations (P600=6,7). For absolute PMDs (P600=6,7) volume units can be specified using this parameter. If needed, absolute PMDs can still use ratiometric (P608=0) to accommodate other units.

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 171

Parameters

Page 181
Image 181
Siemens 200 P608 Flowrate Units MR, Volume units used to display total flow, Million gallons / day Imperial