P834 TVT Start Duration

Use this feature in conjunction with TVT Start Min (P833) to ignore false echoes (or pick up true echoes) near the start of the Echo Profile.

Primary Index

Single Point Model

Dual Point Model

 

 

Global

Transducer

 

 

 

 

Values

Range: 0 to 9999

 

 

 

Preset: 30

 

 

 

 

 

 

Related

• P833 TVT Start Min

 

• P835 TVT Slope Min

 

 

 

 

 

 

Enter the time (in ms) for the TVT Curve to decrease from the TVT Start Min (P833) point to the TVT Curve baseline.

P835 TVT Slope Min

Enter the minimum slope (in dB/s) for the middle of the TVT Curve.

Primary Index

Single Point Model

Dual Point Model

Global

Transducer

 

Values

Range: 0 to 9999

 

 

 

Preset: 200

 

 

 

Related

• P830 TVT Type

 

• P834 TVT Start Duration

 

 

 

 

 

 

Use this feature to adjust the slope declination, and use it in conjunction with TVT Start Duration (when a long flat TVT Type is selected) to ensure the TVT Curve remains above the false echoes in the middle of the Echo Profile. Alternatively, if TVT Type is set for TVT Slopes (P830 = 6), preset is 2000.

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 209

Parameters

Page 219
Image 219
Siemens 200 instruction manual P834 TVT Start Duration, P833 TVT Start Min P835 TVT Slope Min