P336 Auto Record Filling / Emptying

Use this feature to restrict Auto Profile Records from being saved unless the level is rising, falling or either.

Primary Index

Global

 

 

 

 

 

 

 

0

*

Auto Profile Record on filling or emptying

Values

 

 

 

1

 

Auto Profile Record on filling only

 

 

 

 

 

2

 

Auto Profile Record on emptying only

 

 

 

 

 

P334 Auto Record ON Setpoint

 

P335

Auto Record OFF Setpoint

Related

P337 Auto Record LOE Time

 

P702

Filling Indicator

 

P703

Emptying Indicator

 

 

 

 

 

If the level changes at a rate in excess of the corresponding Filling / Emptying Indicator (P702 / P703) values, the Echo Profile is saved subject to this and other Auto Profile Record restrictions.

P337 Auto Record LOE Time

Limits Auto Profile Records from being saved unless extended LOE occurs.

Primary Index

Global

 

 

 

Values

Range: 0.0 to 9999 (seconds)

 

 

 

Preset: 0.0

 

 

 

 

 

P334 Auto Record ON Setpoint

Related

P335

Auto Record OFF Setpoint

 

P336

Auto Record Filling / Emptying

 

 

 

 

If the LOE condition exceeds the period entered, the Echo Profile is saved. When set for 0 LOE is not required for an Auto Profile Record to be saved.

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 163

Parameters

Page 173
Image 173
Siemens 200 instruction manual P336 Auto Record Filling / Emptying, P337 Auto Record LOE Time