P620 Low Flow Cutoff [MR 200]

Eliminates totalizer activity for flows at or below the cutoff value.

Primary Index

 

Single Point Model

Dual Point Model

 

 

 

Global

Transducer

 

 

 

 

Values

Range: 0.000 to 9999

 

 

 

 

Preset = 5.000 %, or equivalent units

 

 

 

 

 

Altered By

P005 Units

 

 

 

 

 

Related

P007 Span

 

 

 

 

 

Use this to enter the minimum head in units (P005) or as a percent of span.

P621 Auto Zero Head [MR 200]

Calibrates Zero Head (P605) based on actual head measurements.

Primary Index

 

Single Point Model

Dual Point Model

 

 

 

 

Global

 

Transducer

 

 

 

 

 

Values

Range: -999 to 9999

 

 

 

 

 

 

P006 Empty

 

Related

P062

Offset Reading

 

P605 Zero Head

 

 

 

 

P664

Temperature

 

 

 

 

 

 

Use this parameter when the reported head is consistently high or low by a fixed amount.

Before using this feature, verify the following parameters are correct:

Empty (P006)

Temperature (P664)

Offset Reading (P062=0)

Zero Head Offset (P605)

Procedure, with “head” steady

1.Press TRANSDUCER to display the calculated head.

2.Repeat step ONE at least FIVE times to verify repeatability.

3.Measure the actual head (with a tape measure or solid rule).

4.Enter the actual head value.

The deviation between the entered Empty (P006) value and the calibrated Empty value is stored in Offset Correction (P652). Alternatively, the Empty parameter (P006) can be corrected directly.

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 173

Parameters

Page 183
Image 183
Siemens 200 instruction manual P620 Low Flow Cutoff MR, P621 Auto Zero Head MR, Procedure, with head steady