Operation

Parameter Indexing

Parameters are indexed when they apply to more than one input or output. The index value defines the input/output for that parameter. Indexed parameters contain a value for each index, even if that index is not used.

MultiRanger Display

The index number and the index values are displayed above the parameter indicator on the LCD.

Index Number

Index Value

1 2 3 4 5 6

Notes

Transducers are always indexed when the dual point option is enabled.

An indexed transducer is commonly referred to as a Point (short for ’Measurement Point’). Point Number refers to indexed transducers.

To set all indexed values for a parameter to the same value, use index 0.

MR 200 only: Transducer parameters are indexed only if Operation (P001) is set to Difference (value=4) or Average (value=5) on a single point MultiRanger.

Accessing a Parameter Index

1.Press DISPLAY once to clear current parameter field.

2.Enter the new parameter number.

3.Press DISPLAY twice.

4.Press the number of the required index. Or press ARROW keys to scroll through the available values.

Note: For optimum performance, set values accurately for indexed parameters. Ensure that the correct index value is being changed for each parameter value.

Page 36

MultiRanger 100/200 – INSTRUCTION MANUAL

7ML19981FB06