Controlling the Display

RUN mode provides numerous parameters and variables that you can track on the display (see Display on page 22).

The LCD displays EEEE if a value is too long.

Adjusting the primary reading for four-digit LCD readout:

Parameter

 

Action

P060

Decimal Position

Sets maximum number of decimals

P061

Convert Reading

Scales the reading to fit

P062

Offset Reading

Shifts the reading up or down by a fixed amount

Example

To reference the displayed level to sea level, enter the distance in Units (P005), between Empty (P006) and sea level. (Enter a negative value if Empty is below sea level.)

 

P006

 

P007

Sea Level

P062

 

 

Reservoir

P062 is the distance between sea level and Empty.

Auxiliary Reading

The Auxiliary Reading area of the LCD displays parameter values while leaving the primary reading on screen.

Note: The parameters shown in the auxiliary reading field are indexed as follows:

global

by transducer

by level

Operation

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 25

Page 35
Image 35
Siemens 200 Controlling the Display, Auxiliary Reading, Adjusting the primary reading for four-digit LCD readout, Action