Setting Simple Level Alarms

To set Relay Five to a standard level alarm (Hi Hi, Hi, Lo, Lo Lo) do the following:

Parameter

Index

Value

Description

 

 

P110

5

1

•

Set P110, indexed to relay, to the value 1 for

 

 

 

 

Transducer One

 

P111

5

1

•

Set P111, indexed to relay, to the value 1 for level

 

 

 

 

alarm

 

 

 

 

 

•

Press UNIT

to display the Auxiliary Function

 

 

 

 

symbol.

 

 

 

 

 

•

Press ARROW keys

as required to scroll

 

 

 

 

to the alarm designation (L, LL, H, or HH).

 

 

 

•

Press ENTER

to enter the value.

P112

5

1.2m

•

Set the ON setpoint

 

P113

5

1.15m

•

Set the OFF setpoint

 

Available designations:

Alarm

Designation

Hi Hi

HH

Hi

H

Lo

L

Lo Lo

LL

Rate [MR 200]

Rate alarms can trigger an alarm if the vessel is filling/emptying too quickly.

Setting a Filling Rate Alarm

Parameter

Index

Value

Description

 

P111

5

4

These settings trip the alarm when the

P112

5

1m

reservoir is filling faster than 1 m per minute

P113

5

0.9m

and reset it at 0.9m per minute.

Setting an Emptying Rate Alarm

 

 

 

 

 

 

 

Parameter

Index

Value

Description

P111

5

4

These settings trip the alarm when the

P112

5

-10%

reservoir is emptying faster than 10% of span

P113

5

-5%

per minute and reset the alarm when

 

 

 

emptying falls to 5%.

Alarms

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 55

Page 65
Image 65
Siemens 200 Rate MR, Setting Simple Level Alarms, Available designations, Alarm Designation, Setting a Filling Rate Alarm