For IN-BOUNDS and OUT-OF-BOUNDS Relay Functions (P111 = 2 and 3 respectively), a dead band prevents relay chatter due to material level fluctuations at both the upper and lower setpoints.

Enter the dead band in either percent of span or units of measure (P005). The dead band value is applied both above and below the upper and lower bound setpoints as shown in the fig- ure.

Actual ON or OFF setpoint

P116

Setpoint set in P112 or P113 P116

Actual OFF or ON setpoint

Parameters

P118 Relay Output Logic

The logic applied to relays to determine the contact open or closed state.

Primary Index

Relay

 

Value

Logic

Alarm

Pump or Control

 

Contact

Contact

Values

 

 

 

 

 

 

 

 

2

*

Positive

Normally Closed

Normally Open

 

 

 

 

 

 

 

 

3

 

Negative

Normally Open

Normally Closed

 

 

 

 

 

 

Related

P111 Relay Control Function

 

The relay contact operation is NORMALLY CLOSED for alarms and NORMALLY OPEN for controls. See P111 Relay Control Function for more information.

Note: P118 is not reset by a master reset (P999).

Power Failure

When power is cut to the MultiRanger, its relays fail to the following states:

 

Relay States

Relay

 

Fail State

 

 

 

1,2,4,5

 

Open

 

 

 

3,6

 

Open or Closed1

1.Relays 3 and 6 are Form C types, so you can wire it either NORMALLY OPEN or NORMALLY CLOSED. Check the wiring before programming.

To use relays 3 or 6 as general alarm indicators, set P118 to 3 – negative logic and wire the alarm for normally open operation. When an alarm event occurs (see below) or when power is cut, the circuit closes and the alarm activates.