Related

(chart cont’d from previous page)

P203 mA Output Value/Transducer

mA Input (P250 to P260) (related only to Value 250)

P800 Near Blanking

P823 Reform Echo

P832 TVT Shaper Adjust

P840 Short Shot Number

P841 Long Shot Number

P842 Short Shot Frequency

P843 Long Shot Frequency

P844 Short Shot Width

P845 Long Shot Width

P852 Short Shot Range

Parameters

P005 Units

Specifies measurement units used for dimensional values.

Primary Index

Global

 

 

1

 

*

Meters

 

 

 

 

 

 

2

 

 

Centimeters

Values

 

 

 

 

3

 

 

Millimeters

 

 

 

 

 

 

4

 

 

Feet

 

 

 

 

 

 

5

 

 

Inches

 

 

P006 Empty

 

P007 Span

 

P603 Maximum Head

Alters

P605 Zero Head

P620 Low Flow Cutoff

 

 

P921 Material Measurement

 

P926 Head Measurement

 

P927 Distance Measurement

 

 

 

 

 

Changing this value automatically changes the units displayed for many parameters. Existing values are converted and do not have to be re-entered.

P006 Empty

Enter distance in units (P005) from the face of the transducer to the process empty point.

Primary Index

Transducer

Values

Range: 0.000 to 99.000 m (or equivalent depending on units)

 

 

 

Preset: 5.000 m (or equivalent depending on units)

 

Alters

P007 Span

Altered By

P005

Units

 

P800

Near Blanking

Related

P921 material Measurement

 

P927 Distance Measurement

 

 

 

 

Setting this value also sets Span (P007) unless Span was already set to another value. For distance operation (P001=3), Span is preset to Empty.

Page 122

MultiRanger 100/200 – INSTRUCTION MANUAL

7ML19981FB06

Page 132
Image 132
Siemens 200 instruction manual P005 Units, P006 Empty, Specifies measurement units used for dimensional values