P215 20 mA Output Trim

Calibrates the 20 mA output.

Primary Index

mA output

 

 

Values

Preset: 20.00

 

 

 

Related

P214 4mA Output Trim

 

 

 

Adjust this value so the device indicates 20.00 mA when P215 is accessed.

mA Output Failsafe (P219) [MR 200]

Please note that this parameter applies to the MultiRanger 200 only.

P219 mA Output Failsafe [MR 200]

Use for failsafe operation, independent of the Failsafe Material Level (P071).

Primary Index

mA output

 

 

 

Range: 0.000 to 22.00

 

 

 

 

 

 

OFF

 

*

mA output responds to Failsafe Material Level (P071).

 

 

 

 

 

Values

HOLd

 

last known value is held until normal operation

 

resumes

 

 

 

 

 

 

 

 

 

 

LO

 

 

produce the Empty mA output immediately

 

 

 

 

 

 

HI

 

 

produce the Span mA output immediately

 

 

 

 

 

Related

P201 mA Output Function

 

 

 

 

 

Selecting an independent mA Failsafe option:

1.Press MODE to display the Auxiliary Function symbol.

2.Press ARROWS to scroll access the failsafe options.

3.Press ENTER when the desired option displayed.

Or, to produce an mA output at a specific value, enter the value required. This is used only if mA output is allocated to a transducer (P201 = 1 to 7).

mA Input (P250 to P260) [MR 200]

Please note that these parameters apply to the MultiRanger 200 only.

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 151

Parameters

Page 161
Image 161