7ML19981FB06 MultiRanger 100/200 – INSTRUCTION MANUAL Page 151
mmmmm
Paramete rs

P215 20 mA Output Trim

Calibrates the 20 mA output.
Adjust this value so the device indicates 20.00 mA when P215 is accessed.
mA Output Failsafe (P219) [MR 200]
Please note that this parameter applies to the MultiRanger 200 only.

P219 mA Output Failsafe [MR 200]

Use for failsafe operation, independent of the Failsafe Material Level (P071).

Selecting an independent mA Failsafe option:

1. Press MODE to display the Auxiliary Function symbol.
2. Press ARROWS to scroll access the failsafe options.
3. Press ENTER when the desired option displayed.
Or, to produce an mA output at a specific value, enter the value required. This is used only
if mA output is allocated to a transducer (P201 = 1 to 7).
mA Input (P250 to P260) [MR 200]
Please note that these parameters apply to the MultiRanger 200 only.
Primary Index mA output
Values Preset: 20.00
Related P214 4mA Output Trim
Primary Index mA output
Values
Range: 0.000 to 22.00
OFF * mA output responds to Failsafe Material Level (P071).
HOLd last known value is held until normal operation
resumes
LO produce the Empty mA output immediately
HI produce the Span mA output immediately
Related P201 mA Output Function