Set the Common Parameters

Prerequisite: Substitute the details of your application in place of the sample values provided. If you are bench testing the unit, set your test values to be the same as the

sample values.

Parameter

P001

P002

P003

P004

P005

P006

P007

Index1

G

G

G

G

G

G

G

Value

1

1

2

102

1

1.8

1.4

Description

Operation = level Material = liquid

Maximum Process Speed = medium Transducer = XPS-10

Units = meters Empty = 1.8m Span = 1.4m

Pump Control

1.Example assumes a single measurement unit. If your MultiRanger has dual point software installed, some parameters are indexed by two.

Set Relays to ALTERNATE DUTY ASSIST

Parameter

Index

 

Value

Description

P111

1

 

52

Sets the pump relays (index 1, 2, and 3) to

P111

2

 

52

 

ALTERNATE DUTY ASSIST.

P111

3

 

52

 

 

Set the Relay ON Setpoints

 

 

 

 

 

 

 

Parameter

Index

 

Value

Description

P112

1

 

0.4m Sets the three setpoints for the pump relays.

P112

2

 

0.3m

The first cycle will use these setpoints.

P112

3

 

0.2m

Subsequent cycles rotate the setpoints

 

 

 

 

among the pumps.

Set the Relay OFF Setpoints

 

 

 

 

 

 

Parameter

Index

 

Value

Description

P113

0

 

1.3m By using index 0 all six relays are set at the

 

 

 

 

same time, including any alarm relays. Use

 

 

 

 

with caution.

For more information, see Appendix D: Pump Control Reference on page 239.