Siemens 200 Failsafe P070 to P072, P070 Failsafe Timer, P071 Failsafe Material Level

Models: 200

1 282
Download 282 pages 42.81 Kb
Page 141
Image 141

Failsafe (P070 to P072)

P070 Failsafe Timer

The time for invalid measurements to elapse before Failsafe State activates.

Primary Index

Single Point Model

Dual Point Model

Global

Transducer

 

Values

Range: 0 to 15 minutes

 

 

 

Preset 10.00 minutes

 

 

 

Altered by

• P003 Maximum Process Speed

 

Related

• P129 Relay Failsafe

 

 

 

 

Once activated, the Failsafe State initiates the following:

1.The material level is reported based on P071 Failsafe Material Level.

The unit responds to the new level as programmed (control and alarm relays activate as defined by the programming).

Individual relays can have independent failsafe responses. See P129 Relay Failsafe.

2.The appropriate error is displayed:

LOE for loss of echo from the transducer

Short for a shorted transducer cable

Open for a cut transducer cable

Error for all other problems

When modifying the preset value, set it short enough to protect the process but long enough to avoid false alarms. Only use No Delay (0.0 Minutes) for testing.

P071 Failsafe Material Level

The material level reported when a Failsafe State is initiated.

Primary Index

Level

 

 

Range: -4999

 

 

Value in units or % (-50% to 150% of span)

 

 

to 9999

 

 

 

 

 

 

 

 

 

Values

 

HI

 

 

Level goes to maximum span

 

 

 

 

 

 

 

 

LO

 

 

Level goes to 0 span (Empty)

 

 

 

 

 

 

 

 

HOLd

*

 

Level remains at last reading

 

P001 Operation

 

 

P006 Empty

 

 

P007 Span

 

Related

P111 Relay Control Function

 

P112 Relay ON Setpoint

 

P113 relay OFF Setpoint

 

P129 Relay Failsafe

 

 

 

 

 

 

Select the Failsafe Material Level based upon the relay operation required during failsafe operation.

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 131