Siemens 200 instruction manual Pump OFF Setpoint R41,430 R41,435, Pumped Volume R41,440 R41,443 MR

Models: 200

1 282
Download 282 pages 42.81 Kb
Page 111
Image 111

Pump OFF Setpoint (R41,430 – R41,435)

The OFF setpoint level (P113) for the referenced pump relay.

The setpoint is scaled from 0 to 10,000 (0 to 100% of span multiplied by 100). So 54.02% is shown in the register as 5402.

Pumped Volume (R41,440 – R41,443) [MR 200]

The pumped volume registers hold the current total for all of the pumps associated with a level point. These registers are available only if operation is set to pumped volume (P001 = 7).

These volumes can become very large. Therefore, two registers are used to hold the value. See Unsigned Double Precision Integer (UINT32) on page 107 for more information.

The value in the registers is given as an integer value but must be interpreted as having the number of decimals set in P633 (LCD Totalized Decimal Position): this number can be 0 to 3. Ensure that your software accounts for these decimal places before you report the pumped volume totals.

Pump Hours (R41,450 – R41,461)

The number of running hours for the referenced pump relay. The hours are given to three decimal places, so the integer must be divided by 1000 to get the correct value. For example 12,340 represents 12.34 hours.

This value comes from parameter P310. See page 157 of the Parameter Reference section for details.

Pump Starts (R41,470 – R41,475)

The number of pump starts for the referenced pump relay.

This value comes from parameter P311. See page 157 of the Parameter Reference section for details.

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 101

Modbus Register Types

Page 111
Image 111
Siemens 200 Pump OFF Setpoint R41,430 R41,435, Pumped Volume R41,440 R41,443 MR, Pump Hours R41,450 R41,461