Siemens 200 External Totalizers and Flow Samplers MR, Relay Contacts, Counter Formula

Models: 200

1 282
Download 282 pages 42.81 Kb
Page 81
Image 81

External Totalizers and Flow Samplers [MR 200]

This feature is only available on the MultiRanger 200.

External totalizers are simple counters which count the number of relay clicks produced by the MultiRanger. This is generally used to keep track of OCM or pumped volume totals. Note that both of these values are also stored in the MultiRanger and are available through communications.

Flow samplers are devices which take a sample of liquid when triggered by a relay click. These samples are used to monitor water quality over time. Flow samplers can be driven by OCM volume or by relay click volume settings depending on the application requirements.

Relay Contacts

Pumped volume is calculated at the end of the pump cycle. Totalized volume given through a relay set up for totalizer (P111[r]=40) will be given in bursts at this time.

Both the open and closed times for the relay contact are provided by P645 and are preset to 0.2 seconds. Partial units are added to the next pump cycle.

Example:

Shows a relay set up to make one contact for every cubic metre (m3) of liquid.

P645

 

 

 

 

 

 

 

 

 

 

 

P645

 

 

 

 

 

 

 

 

 

 

 

 

 

4m3

2m3

2m3

3m3

1m3

Pump Cycle

Totalizer

To set the totalizer to provide relay contact to an external counter, use the following:

 

 

 

Counter Formula

 

 

 

1 Contact per 10P640 units

 

P640 is preset to 0 so the default number of

 

 

 

 

 

 

contacts for a pumped volume cycle is

 

 

 

 

 

 

equivalent to the number of volume units.

 

 

 

 

 

 

 

 

 

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 71

External Totalizers and Flow Samplers – MR 200

Page 81