P110 Level Source

Sets the level source on which the indexed relay is assigned to a measurement point. Please note that Difference and Average settings are MultiRanger 200 features.

Primary Index

Relay

 

 

 

 

Range: 1 to 3

 

 

 

 

 

 

 

 

 

 

1

*

Point # 1

= Transducer One

Values

 

 

 

 

 

 

2

 

Point # 2

= Transducer Two

 

 

 

 

 

 

 

 

3

 

Point # 3

= Difference (P001=4) or Average (P001=5)

 

[MR 200]

 

[MR 200]

 

P003

Maximum Process Speed

 

P700 Max Fill rate

 

Altered by:

P701 Max Empty rate

 

P070 Failsafe Timer

 

P071 Failsafe Material Level

 

 

 

 

 

 

MultiRanger 200

Please note that these features are only available on the MultiRanger 200.

In Single Point Mode (standard):

Points 2 and 3 are available only if Operation is set for difference or average (P001 = 4 or 5).

In Dual Point Mode (optional):

Point 2 is always available, and Point 3 is available only if Operation is set for difference or average (P001 = 4 or 5).

P111 Relay Control Function

Sets the control algorithm used to trip the relay.

Please note that parameter P111 values vary between the MultiRanger 100 and the MultiRanger 200.

Primary Index

Relay

Values

See chart below

Altered by

P100 Preset Applications

 

 

 

Use zero 0 (preset) to disable control of the indexed relay.

Note: All relay ON/OFF points must be referenced from Empty (P006), regardless of Operation Mode selection (POO1).

Page 134

MultiRanger 100/200 – INSTRUCTION MANUAL

7ML19981FB06