P055 Volume Breakpoints and Characterization (Universal Volume Calculation) [MR 200]

Each segment defined by the level breakpoints (P055) requires a volume so that the MultiRanger can make the level-to-volume calculations.

Primary Index

Level

Secondary Index

Breakpoint

Values

Range: 0.0 to 99999

Related

P054 Breakpoints Levels (Universal Volume Calculation)

 

 

 

Typical volume calculations

ConeCylinder

V = (1/3)πr2h

V = πr2h

Entering a Volume Breakpoint

1.Go to Parameter P055.

2.For each index enter a volume.

3.Ensure that each volume corresponds to the same index for P054.

For more on Volume Characterization, go to page 52.

Display and Reading (P060 to P062)

These parameters are used to:

Change the number of decimal places displayed

Convert the Reading to alternate units

Reference measurements to other than Empty (P006) or Span (P007)

P060 Decimal Position

Defines the maximum number of decimal places used on the LCD.

Primary Index

Level

 

 

 

0

 

 

No digits after the decimal point

 

 

 

 

 

Values

1

 

 

1 digit after the decimal point

 

 

 

 

2

 

*

2 digits after the decimal point

 

 

 

 

 

 

 

 

3

 

 

3 digits after the decimal point (limited by device resolution)

 

 

 

 

 