P728 Shot Delay

The delay, in seconds, between transducer shots.

Primary Index

Transducer

Range: 0.1 to 4.0

Values

Preset: 0.5

Use this if transient acoustic noise within the vessel is causing measurement difficulties due to echoes from one shot being received on the next. If more than one ultrasonic unit is installed for redundancy, this value should be 0.

P729 Scan Time

View the elapsed time (in seconds) since the point displayed was last scanned.

Primary Index

Level

 

 

 

Values

Range: 0.000 to 9999 (view only)

 

 

 

Related

P001 Operation

 

 

 

This may be viewed as an Auxiliary Reading in the RUN mode.

Display (P730 to P739)

P730 Auxiliary Reading

Use this feature to display operator selected Auxiliary Readings temporarily or indefinitely (as desired).

Primary Index

Global

Range: 000 to 999

Values

Display: OFF, HOLd

Select OFF to display Auxiliary Readings temporarily. Select HOLd to display Auxiliary Readings until another Auxiliary Reading is selected or programming mode is entered. See the Hand Programmer section on page 27 for RUN mode auxiliary readings.

Selecting the Auxiliary Reading operation

1.Press READING to display the Auxiliary Function symbol.

2.Press ARROWS to access the OFF or HOLd option desired.

3.Press ENTER