(Screen) Control

MR 200

Rake

 

 

 

Setting the Common Parameters

Prerequisite: Substitute the details of your application in place of the sample values provided. If you are bench testing the unit, set your test values to be the same as the sample values.

Parameter

Index

Value

Description

 

P001

G

4

Operation

= Differential

P002

G

1

Material

= liquid

P003

1,2

2

Max. Process Speed

= medium

P004

1,2

102

Transducer

= XPS-10

P005

G

1

Units

= meters

P006

1

1.8

Empty

= 1.8m

 

2

2.2

Empty

= 2.2m

P007

1

1.4

Span

= 1.4m

 

2

1.4

Span

= 1.4m

 

3

1.4

Max Differential

= 1.4m

Set Relay 1 (Operate Rake)

Parameter

Index

Value

Description

P110

1

3

Starts the rake when the difference between the

P111

1

50

two levels rises above 0.4m and stop the rake

P112

1

0.4

when the difference falls below 0.1m.

P113

1

0.1

 

Set Relays 2 to 4 (Level Alarms)

P110

2

1

Description

P110

2

1

Sets Relay Two as a high level alarm for

P111

2

1

Transducer One with an ON setpoint of 1.3m

P112

2

1.3

and an OFF setpoint of 1.2m.

P113

2

1.2

 

P110

3

2

Sets Relay Three as a low level alarm for

P111

3

1

Transducer Two with an ON setpoint of 0.2m

P112

3

0.2

and an OFF setpoint of 0.4m.

P113

3

0.4

 

P110

4

3

Sets Relay Four as a rake failure alarm as it

P111

4

1

uses the differential level point (3) with an

P112

4

1.0

ON setpoint of 1.0m and an OFF setpoint of

 

 

 

0.9m.

P113

4

0.9

 

Page 70

MultiRanger 100/200 – INSTRUCTION MANUAL

7ML19981FB06

Page 80