P712 Echo Lock Sampling

The sampling criterion sets the number of consecutive echoes appearing above or below the echo currently locked onto, that must occur before the measurements are validated as the new reading (for Echo Lock P711 values: 1 or 2).

Primary Index

Single Point Model

Dual Point Model

 

 

Global

Transducer

 

 

 

 

 

Range: 1:1 to 50:50

 

 

 

 

Values

Format: x:y

 

 

 

x = the number of above echoes

 

 

 

 

 

 

 

y = the number of below echoes

 

 

 

 

Related

• P711 Echo Lock

 

 

 

 

P711 value

P712 preset value

1, max verification

5:5

 

 

2, material agitator

5:2

 

 

Example:

Setting

P711 = 2, material agitator

P712 = 5:2

Result

a new reading will not be validated unlessfive consecutive measurements higher or two consecutive measurements lower than the current reading occur

Resetting P711 returns P712 to the respective preset values

P713 Echo Lock Window

Adjusts the size of the Echo Lock Window.

 

Primary Index

 

Single Point Model

Dual Point Model

 

 

 

 

 

 

 

 

Global

Transducer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Range: 0.000 to 99.00 m (or equivalent depending on units), nearest

 

 

Values

 

acceptable value is returned

 

 

 

 

 

 

 

 

 

 

 

 

 

Preset: 0.000

 

 

 

 

 

 

 

 

 

 

 

Altered by

 

P003 Maximum Process Speed

 

 

 

 

 

 

 

 

 

 

 

Related

 

P005 Units

 

 

 

 

 

P711 Echo Lock

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 189

Parameters