Pump Control

Set Relays to FIXED DUTY BACKUP [MR 200]

Parameter

Index

 

Value

 

Description

 

 

P111

1

51

 

Sets the pump relays (index 1, 2, and 3) to

P111

2

51

 

FIXED DUTY BACKUP. Only one pump will

P111

3

51

 

ever run at one time.

Set the Relay ON Setpoints [MR 200]

 

 

 

 

 

 

Parameter

Index

 

Value

 

Description

P112

1

 

0.4m

 

Sets the three setpoints for the pump relays.

P112

2

 

0.3m

 

The setpoints remain attached to the pump

P112

3

 

0.2m

 

relays.

Set the Relay OFF Setpoints [MR 200]

 

 

 

 

 

 

Parameter

Index

 

Value

 

Description

P113

0

 

1.3m By using index 0 all six relays are set at the

 

 

 

 

 

same time, including any alarm relays. Use

 

 

 

 

 

with caution.

Set Relays to ALTERNATE DUTY SERVICE [MR 200]

Parameter

Index

Value

 

Description

P111

1

 

54

 

Sets the pump relays (index 1, 2, and 3) to

P111

2

 

54

 

 

 

SERVICE RATIO DUTY ASSIST

P111

3

 

54

 

 

 

 

P122

1

 

25

 

Sets the ratio to: 25% – Pump One

P122

2

 

50

 

50% – Pump Two

 

 

 

 

 

25% – Pump Three

P122

3

 

25

 

Set the Relay ON Setpoints [MR 200]

 

 

 

 

 

 

Parameter

Index

 

Value

Description

P112

1

 

0.4m Sets the three setpoints for the pump relays.

P112

2

 

0.3m

The first cycle will use these setpoints.

P112

3

 

0.2m

Subsequent cycles rotate the setpoints

 

 

 

 

among the pumps.

Set the Relay OFF Setpoints [MR 200]

 

 

 

 

 

 

Parameter

Index

 

Value

 

Description

P113

0

 

1.3m By using index 0 all six relays are set at the

 

 

 

 

 

same time, including any alarm relays. Use

 

 

 

 

 

with caution.

Page 62

MultiRanger 100/200 – INSTRUCTION MANUAL

7ML19981FB06