Pump Control

Example:

The flush valve connects to Relay Four and the watched pump is on Relay One.

Parameter

Index

Value

Description

P170

G

1

Watch Relay One to count pump cycles.

P171

G

3

Open the flush valve for 3 cycles.

P172

G

10

Use the flush value every 10 cycles.

P173

G

120

Open the flush valve for 120 seconds.

Relay Controlled by Communications

A relay can be controlled directly by a remote system through communications. No other control schemes can then be used with a relay configured this way. Communications can be used to force status of some control relays, such as pumps.

Settings:

Parameter

Index

Value

Description

P111

5

65

Sets Relay Five to communications control.

Tracking Pump Usage

You can find out how much an individual pump has been used by viewing the pump records parameters.

Information Available

Parameter Access

Current RUN time

P309

Total pump hours

P310

Total pump starts

P311

Total pump RUN on occurrences

P312 [MR 200 ONLY]

Page 68

MultiRanger 100/200 – INSTRUCTION MANUAL

7ML19981FB06

Page 78
Image 78
Siemens 200 Tracking Pump Usage, Relay Controlled by Communications, Information Available Parameter Access