Set Relays to ALTERNATE DUTY ASSIST

Parameter

Index

Value

Description

P111

1

52

Sets the pump relays (index 1, 2, and 3) to

P111

2

52

ALTERNATE DUTY ASSIST.

P111

3

52

 

Set the ON Setpoints

 

 

 

 

 

 

Parameter

Index

Value

Description

P112

1

1.0m

Sets the three setpoints for the pump relays.

P112

2

1.1m

The first cycle will use these setpoints.

P112

3

1.2m

Subsequent cycles rotate the setpoints

 

 

 

among the pumps.

Set the OFF Setpoints

 

 

 

 

 

 

Parameter

Index

Value

Description

P113

0

0.5m By using index 0 all six relays are set at the

 

 

 

same time, including any alarm relays. Use

 

 

 

with caution.

Setting a Pump Up (Reservoir) Group

Sets a group of three pumps to pump up a reservoir.

MultiRanger

Pump Control

Inflow

P006

P007

Outflow

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 59

Page 69