Siemens 200 instruction manual P641 Flow Sampler Mantissa MR, P642 Flow Sampler Exponent MR

Models: 200

1 282
Download 282 pages 42.81 Kb
Page 187
Image 187

Enter the factor (powers of 10 only) by which actual volume is divided, prior to Remote Totalizer count increment.

Example:

For a Remote Totalizer update by 1000s of volume units, enter 3.

P641 Flow Sampler Mantissa [MR 200]

Use this feature in conjunction with Flow Sampler Exponent (P642) to establish the number of flow units required to increment the Flow Sampler (device connected to the MultiRanger relay set for the flow sampler operation Relay Function, P111 = 41).

Primary Index

Single Point Model

 

Dual Point Model

 

 

 

Global

 

Transducer

 

 

 

 

 

 

Values

Range: 0.001 to 9999

 

 

 

 

Preset = 1.000

 

 

 

 

 

 

 

• P001 Operation

 

Related

• P111 Relay Control Function

 

• OCM (P600 to P621)

 

 

 

 

• P642 Flow Sampler Exponent

 

 

 

 

 

This parameter is relevant only if Operation is set to OCM (P001 = 6).

Enter the mantissa (Y) for the exponent (Z) in the formula:

Flow Sampler Increment = Y x 10Z Flow units.

Example: To count once every 4310 (4.31 x 103) flow units:

set P641 to 4.31 and P642 to 3

P642 Flow Sampler Exponent [MR 200]

Use this feature in conjunction with Flow Sampler Mantissa (P641) to establish the number of flow units required to increment the Flow Sampler (device connected to the MultiRanger relay set for the flow sampler operation Relay Function, P111 = 41).

 

Primary Index

Single Point Model

 

Dual Point Model

 

 

 

 

 

 

 

 

Global

 

Transducer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Values

 

Range: -3 to +7 (integers only)

 

 

 

 

 

 

 

 

 

 

 

 

Preset = 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• P001 Operation

 

 

 

 

Related

 

• P111 Relay Control Function

 

 

 

 

 

• OCM (P600 to P621)

 

 

 

 

 

 

 

 

 

 

 

 

• P641 Flow Sampler Mantissa

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 177

Parameters

Page 187
Image 187
Siemens 200 instruction manual P641 Flow Sampler Mantissa MR, P642 Flow Sampler Exponent MR