P772 Baud Rate

The communication rate with the master device.

Primary Index

Communications Port

 

 

 

 

 

4.8

 

4800 baud

 

 

 

 

Values

9.6

 

9600 baud

 

 

 

19.2

*

19,200 baud (preset for port 2)

 

 

 

 

 

 

115.2

*

115,200 baud (preset for port 1)

 

 

 

 

This specifies the rate of communication in Kbaud. Any value may be entered but only the values shown above are supported. The baud rate should reflect the speed of the connected hardware and protocol used.

P773 Parity

The serial port parity.

Primary Index

Communications Port

 

 

 

 

 

0

*

No Parity

Values

 

 

 

1

 

Odd Parity

 

 

 

 

 

2

 

Even Parity

 

 

 

 

Ensure that the communications parameters are identical between the MultiRanger and all connected devices. For example, many modems default to N-8-1 which is No parity, 8 data bits, and 1 stop bit.

P774 Data Bits

The number of data bits per character.

Primary Index

Communications Port

 

Range: 5 to 8

 

 

 

 

 

 

8

*

Modbus RTU

 

 

 

 

Values

7 or 8

 

Modbus ASCII

 

 

 

 

7 or 8

 

Dolphin Plus

 

 

 

 

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 195

Parameters

Page 205
Image 205
Siemens 200 instruction manual P772 Baud Rate, P773 Parity, P774 Data Bits