Operation

Example [MR 200 only]

P054 provides up to 32 breakpoint levels used with P055 (Volume Breakpoint) for universal volume calculation. The illustration indicates how you can set secondary indexes to specific functions.

 

A

 

B

C

P054

[1,6] = 2m

P054

[1,3] = 1.5m

P054 [1,1] = .75m

P054

[2,6] = 8m

P054

[2,3] = 5.5m

P054 [2,1] = 2.75m

 

 

P054

 

 

1

 

 

2

[6 = 2m]

[3 = 1.5m]

[1 = 0.75m]

A

A

B

B

C C

[6 = 8m]

[3 = 5.5m]

[1 = 2.75m]

P054 [1,1] = .75m sets breakpoint 1 on transducer 1 to .75m.

P054 [2,1] = 8m sets breakpoint 1 on transducer 2 to 2.75m.

Starting Measurement

The MultiRanger startup varies between single and dual point models.

Note: The number of points is an order option and is set by the factory. On a single point model, the index for P001 is global (G). On a dual point model the index for P001 is 1 or 2. To check the model in use, enter P001 on handheld programmer. For a single point device, parameter P001 will not show an entry for index number on the LCD. (See MultiRanger Display on page 36 for location of index number on the LCD.) Parameter P001 will display an index number for a dual point model.

Single Point Models

The MultiRanger starts in DISTANCE mode with the transducer preset for the XPS-10 and an empty distance of 5 meters. Change the following parameters to reflect your application parameters.

Parameter

P001

P002

P003

P004

P005

P006

P007

Index

G

G

G

G

G

G

G

Value

1

1

2

104

1

12

10

Description

Operation = level Material = liquid

Maximum Process Speed = medium Transducer = XPS-15

Units = meters Empty = 12m Span = 10m

Page 38

MultiRanger 100/200 – INSTRUCTION MANUAL

7ML19981FB06

Page 48
Image 48
Siemens instruction manual Starting Measurement, Single Point Models, Example MR 200 only, Parameter, Index Value