Parameters

Selecting HI, LO, or HOLd

1.Press FUNCTION to display the Auxiliary Function symbol.

2.Press ARROWS to scroll to the desired option.

3.Press ENTER to set the value.

Entering a Measurement

To enter a specific Failsafe Material Level within -50 to 150% of Span (P007), in Units (P005).

Relay reaction

The way in which relay programming reacts to the failsafe level depends on P129 Relay Failsafe (page 140). By default:

Alarm relays have P129 = OFF and so react to the Failsafe Material Level.

Control relays have P129 = dE and so de-energize the relay when the unit enters Failsafe mode regardless of the Failsafe Material Level.

P072 Failsafe Level Advance

Sets the speed the MultiRanger advances to and returns from the Failsafe Material Level.

Primary Index

Level

 

 

1

*

Restricted

Advances to/from Failsafe Material Level as set by

 

P003, P700 and P701.

 

 

 

 

Values

 

 

 

 

2

 

Immediate

Failsafe Material Level assumed right away

 

 

 

 

 

 

3

 

Fast Back

Failsafe Level Advance is restricted, return is

 

 

immediate

 

 

 

 

 

P003 Maximum Process Speed

 

P070 Failsafe Timer

Related

P071 Failsafe Material Level

 

P700 Max Fill rate

 

P701 Max Empty rate

 

 

 

 

 

Relays (P100 to P119)

The MultiRanger has three or six relays (or digital outputs) used to control devices and alarms. While the number of devices is limited by the relays, all control functions are accessible through software and each parameter is indexed to the three or six relays. See the Relay section on page 41.

Preset Applications (P100)

The MultiRanger makes standard applications easier to program by providing an extensive list of presets.

Page 132

MultiRanger 100/200 – INSTRUCTION MANUAL

7ML19981FB06

Page 142
Image 142
Siemens 200 instruction manual Relays P100 to P119, P072 Failsafe Level Advance