Other Pump Control Algorithms

Set Relays to ALTERNATE DUTY BACKUP [MR 200]

Parameter

Index

 

Value

Description

 

P111

1

53

Sets the pump relays (index 1, 2, and 3) to

P111

2

53

ALTERNATE DUTY BACKUP.

P111

3

53

 

Set the Relay ON Setpoints [MR 200]

 

 

 

 

 

Parameter

Index

 

Value

Description

P112

1

 

0.4m Sets the three setpoints for the pump relays.

P112

2

 

0.3m

The first cycle will use these setpoints.

P112

3

 

0.2m

Subsequent cycles rotate the setpoints

 

 

 

 

among the pumps.

Set the Relay OFF Setpoints [MR 200]

 

 

 

 

 

Parameter

Index

 

Value

Description

P113

0

 

1.3m By using index 0 all six relays are set at the

 

 

 

 

same time, including any alarm relays. Use

 

 

 

 

with caution.

Set Relays to FIXED DUTY ASSIST

Parameter

Index

Value

Description

P111

1

50

Sets the pump relays (index 1, 2, and 3) to

P111

2

50

FIXED DUTY ASSIST. Multiple pumps can run

P111

3

50

simultaneously.

Set the Relay ON Setpoints

 

 

 

 

 

 

Parameter

Index

Value

Description

P112

1

0.4m

Sets the three setpoints for the pump relays.

P112

2

0.3m

The setpoints remain attached to the pump

P112

3

0.2m

relays.

Set the Relay OFF Setpoints

 

 

 

 

 

Parameter

Index

Value

Description

P113

0

1.3m

By using index 0 all six relays are set at the

 

 

 

same time, including any alarm relays. Use

 

 

 

with caution.

Pump Control

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 61

Page 71
Image 71
Siemens 200 Other Pump Control Algorithms, Set Relays to Fixed Duty Assist, Set the Relay on Setpoints MR