Appendix F: Upgrading

MultiRanger Plus to MultiRanger 100/200 Parameters

The MultiRanger 100/200 uses the current Siemens Milltronics standard parameter set which is different than the parameter numbers used in the MultiRanger Plus.

The MultiRanger Plus parameters numbers are sequential (P-0 to P-99). The MultiRanger 100/200 parameters number are also sequential; however, some of the parameters are indexed.

Parameters are indexed when they apply to more than one input or output. The index value defines the input/output for that parameter. Indexed parameters contain a value for each index, even if that index is not used.

Example

In the MultiRanger Plus each relay had a dedicated parameter number for its function, ON and OFF points.

MultiRanger Plus Relay One

P-8: Function

P-9 : ON setpoint

P-10: OFF setpoint

MultiRanger 100/200 uses P111 for all relays and indexes these parameters.

P-111: Function

P-112: ON

P-113: OFF

The following tables show the differences between the MultiRanger Plus and the MultiRanger 100/200. They each show one relay programmed as a high alarm, and two relays programmed for pump control with alternating pump starts:

MultiRanger Plus

Relay

Parameter

Value

1

P-8 (relay function)

1 (alarm)

 

 

 

1

P-9 (ON setpoint)

4 m

 

 

 

1

P10 (OFF setpoint)

3.5 m

 

 

 

2

P-11 (relay function)

9

 

 

 

 

2

P-12

(ON setpoint)

3.2 m

 

 

 

 

2

P-13

(OFF setpoint)

0.5 m

 

 

 

 

3

P-14

(relay function)

9

 

 

 

3

P-15 (ON setpoint)

3.4 m

 

 

 

3

P-16 (OFF setpoint)

0.6 m

 

 

 

 

MultiRanger 100/200

Relay

Parameter

Value

1

P111 [1]

(relay function)

1

 

 

 

1

P112 [1] (ON setpoint)

4 m

 

 

 

 

1

P113[1]

(OFF setpoint)

3.5 m

 

 

 

 

2

P111[2]

(relay function)

52

 

 

 

 

2

P112[2]

(ON setpoint)

3.2 m

 

 

 

 

2

P113[2]

(OFF setpoint)

0.5 m

 

 

 

 

3

P111[3]

(relay function)

52

 

 

 

 

3

P112[3]

(ON setpoint)

3.4 m

 

 

 

 

3

P113[3]

(OFF setpoint)

0.6 m

 

 

 

 

Page 248

MultiRanger 100/200 – INSTRUCTION MANUAL

7ML19981FB06

Page 258
Image 258
Siemens 200 instruction manual MultiRanger Plus, Relay Parameter Value, Alarm, On setpoint