Appendix E: Updating Software

Updating Software

To update the software in the MultiRanger, please contact your Siemens Milltronics representative to obtain the software. For a complete list of representatives, go to www.siemens.com/processautomation.

WARNINGS:

1.All parameter values will be lost during software upgrade. Record your current parameters manually or using Dolphin Plus or SIMATIC PDM before upgrade.

2.Disable all pumps and alarms before updating software, as relays can change state during the software update causing pumps to turn on or off .

To install the software, please complete the following:

1.Connect your PC or laptop to the MultiRanger RJ-11 RS-232 port.

2.Run the .exe Downloader program in the software. Use this to set the RS-232 settings to match your MultiRanger. Please note that the software default settings will already match the default settings of the unit. Changes are only necessary if the RS-232 settings in the unit have been changed.

3.Complete the Downloader program steps.

4.Verify that Downloader confirms a succesful upgrade before exiting.

5.Complete a Master Reset (P999) after a successful upgrade, before re-entering parameters.

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 245

Appendix E: Updating Software

Page 255
Image 255
Siemens 200 instruction manual Appendix E Updating Software