P171 Flush Cycles [MR 200]

Sets the number of pump cycles requiring flush control.

Primary Index

Single Point Model

Dual Point Model

 

 

Global

Relay

 

 

 

 

Values

Range: 0 to 9999

 

 

 

Preset: 0

 

 

 

 

 

 

Related

• P111 = 64, Flush Valve

 

 

 

 

If three flush cycles are required after every ten pump cycles then:

P172 (Flush Interval) = 10

P171 (Flush Cycles) = 3

P172 Flush Interval [MR 200]

Sets the number of pump cycles before flush control is enabled.

Primary Index

Single Point Model

Dual Point Model

 

 

Global

Relay

 

 

 

 

Values

Range: 0 to 9999

 

 

 

Preset: 0

 

 

 

 

 

 

Related

• P111 = 64, Flush Valve

 

 

 

 

To start a new flush cycle every ten times the pumps are run, set this to 10.

P173 Flush Duration [MR 200]

The length of time for each flush cycle that the flush control is active.

Primary Index

Single Point Model

Dual Point Model

 

 

Global

Relay

 

 

 

 

Values

Range: 0.000 to 9999 s

 

 

 

Preset: 0.000

 

 

 

 

 

 

Related

• P111 = 64, Flush Valve

 

 

 

 