Parameters

Please note the following:

enter value in current units (as selected in P005)

valid for level, space, and distance

volume is calculated based on the Backup level

Example:

Transducer One is configured for a level measurement. Digital Input 2 is connected to a Hi Level Backup switch located a level of 4.3m.

Parameter

Index

Value

P064

1

2

 

 

 

P065

1

4.3

 

 

 

When the level rises to 4.3m, and the switch is activated, the reading is forced to 4.3m. The reading stays at 4.3m until the switch is de-activated.

P066 Override Time Delay

Defines the time used to calm (debounce) the override condition input. Set in seconds.

Primary Index

Transducer

Values

Range: 0.0 to 9999

Preset: 5.0

 

 

P064

Override Enable

Related

P065

Reading Override Value

 

P270

Discrete Input Function

 

 

 

 

Note: Activation of the Level Override is subject to the measurement cycle. This can add up to four seconds to the overall response time depending on operating conditions and programming.

P069 Password

Holds the current password for P000. Select by typing in 069. You cannot scroll to this parameter.

Primary Index

Global

Values

Range: 0 to 9999

Default: 1954

 

Related

P000 Lock

 

 

 

This parameter is write-only, and can only be selected by entering 069. To change the password, unlock the device by entering the current password into P000. Then enter the new password into P069. To lock the device, enter a password other than the correct one in P000. While the device is unlocked, the password is visible in P000.

Page 130

MultiRanger 100/200 – INSTRUCTION MANUAL

7ML19981FB06

Page 140
Image 140
Siemens 200 instruction manual P066 Override Time Delay, P069 Password