Siemens 200 Standard Data Logging P300 to P321, Record Temperatures P300 to P303, Range of Values

Models: 200

1 282
Download 282 pages 42.81 Kb
Page 164
Image 164

Parameters

P270 Discrete Input Function

Sets how discrete signals are interpreted by the MultiRanger.

Primary Index

Discrete input

 

 

 

 

 

0

 

Forced OFF

 

 

 

 

Values

1

 

Forced ON

 

 

 

2

*

Normally Open – 0 (DI open), 1 (DI closed)

 

 

 

 

 

 

3

 

Normally Closed – 0 (DI closed), 1 (DI open)

 

 

 

 

Related

Pump Control section

 

 

 

 

P275 Scaled Discrete Input Value

Shows the current value of the discrete input after any scaling is applied.

Primary Index

Discrete input

 

 

 

Display: view only

 

 

 

Values: dependent on the function of the discrete input

 

Range of Values

Function (P270)

 

 

 

Values

1

Forced ON

 

 

 

 

0

Forced OFF

 

 

 

 

0 (DI open), 1 (DI closed)

Normally Open

 

 

 

 

0 (DI closed), 1 (DI open)

Normally Closed

 

 

 

Readings are updated continuously even in PROGRAM mode. The value signals a level override event.

Standard Data Logging (P300 to P321)

All records can be reset by pressing the CLEAR keys.

Record Temperatures (P300 to P303)

These features display the high and/or low temperatures in °C. When a parameter relating to a TS-3 Temperature Sensor is accessed, the Point Type display changes to the

TS-3 symbol .

If the unit is powered up without a temperature sensor connected, the value –50°C is displayed. This information can help trace problems with both built in and external temperature sensors.

Page 154

MultiRanger 100/200 – INSTRUCTION MANUAL

7ML19981FB06

Page 164
Image 164
Siemens 200 Standard Data Logging P300 to P321, Record Temperatures P300 to P303, P270 Discrete Input Function