P003 Maximum Process Speed

Determines level change reaction.

Primary Index

Transducer

 

1

 

 

 

Slow (0.1 m/min)

Values

 

 

 

 

 

2

 

*

 

Medium (1 m/min)

 

 

 

 

 

 

 

3

 

 

 

Fast (10 m/min)

 

 

P070

Failsafe Timer

 

P700 Max Fill Rate

 

P701 Max Empty Rate

 

P702

Filling Indicator

Alters

P703

Emptying Indicator

P704

Rate Filter

 

 

P710

Fuzz Filter

 

P713 Echo Lock Window

 

P727 Scan Delay

 

P841 Long Shot Number

 

Failsafe (P070 to P072)

 

P121 Pump by Rate

Related

Rate (P700 to P708)

Measurement Verification (P710 to P713)

 

 

Transducer Scanning (P726 to P729)

 

P905

Transmit Pulse

 

 

 

 

 

 

Use a setting just fast enough to keep up with your process. Slower settings provide higher accuracy. Faster settings allow for more level fluctuations.

P004 Transducer

Specifies the Siemens Milltronics transducer connected to the unit.

Primary Index

Single Point Model

Dual Point Model

Global

 

Transducer

 

 

 

0

*

No transducer attached

(preset for Dual Point)

 

1

 

ST-25

 

 

2

 

ST-50

 

 

100

 

STH

 

 

101

 

XCT-8

 

Values

102

*

XPS-10 (preset for Single Point Model)

 

103

 

XCT-12

 

 

104

 

XPS-15

 

 

112

 

XRS-5

 

 

250

 

mA input [MR 200]

 

(chart con’t next page)

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 121

Parameters

Page 131
Image 131