P782 Parameter Index Location

Determines where index information is stored for the parameter access area.

Primary Index

Global

0 * Global

Values

1Parameter-Specific

Altered By

P770 Port Protocol

Global (0)

The primary and secondary index values are global (they affect all of the parameter access area at once) and stored in:

primary index – R43,999

secondary index – R43,998

Parameter-Specific (1)

The primary and secondary index values are encoded into the format words found between R46,000 and R46,999. Each format work corresponds with the R44,000 series number in the parameter access map. For example, the format register R46,111 corresponds to the parameter P111 and the value is stored in R44,111. If the Modbus protocol (P770 = 2 or 3) is not used this parameter is ignored.

SmartLinx Hardware Testing (P790 to P795)

Note: These parameters are used to test and debug a SmartLinx card (if installed). Disregard these parameters if you do not have a SmartLinx card installed.

P790 Hardware Error

The results of ongoing hardware tests in the communications circuitry.

Primary Index

Global

 

 

 

 

 

 

 

PASS

*

No errors

 

 

 

 

 

 

FAIL

 

 

Error occurred communicating with card; commu-

Values

 

 

nications should resume.

 

 

 

 

 

 

 

 

 

ERR1

 

No module installed, or module not supported;

 

 

SmartLinx communications have been disabled

 

 

 

 

 

 

 

 

 

Related

P791 Hardware Error Code

P792 Hardware Error Count

 

 

 

 

 

 

If FAIL or ERR1 is displayed in P790 (Hardware Error), go to P791 (Hardware Error Code) and P792 (Hardware Error Count) for information about the error.

7ML19981FB06

MultiRanger 100/200 – INSTRUCTION MANUAL

Page 197

Parameters

Page 207
Image 207
Siemens 200 SmartLinx Hardware Testing P790 to P795, P782 Parameter Index Location, P790 Hardware Error, Global